DX系列 濕式差壓開(kāi)關(guān)-德威爾Dwyer

點(diǎn)擊圖片查看原圖
品牌: 德威爾Dwyer
單價(jià): 面議
所在地: 上海
有效期至: 長(zhǎng)期有效
最后更新: 2018-07-19 09:43
瀏覽次數(shù): 678
詢價(jià)
店鋪基本資料信息
 
產(chǎn)品詳細(xì)說(shuō)明
DX系列 濕式差壓開(kāi)關(guān)-德威爾Dwyer

The SERIES DX is a differential pressure switch that makes a contact output based on the differential between two pressure sources. Wetted materials of brass and flouroelastomer are suitable for use with most gases and water based solutions. The switch can be used for low differential pressure indication with set point on a decrease of pressure as low as 1 psid (0.07 bar). Differential set point ranges are available from 2.5 to 75 psid (0.17 to 5.17 bar) on increasing differential pressure and 1.0 to 67 psid (0.07 to 4.62 bar) on decreasing differential pressure. Unit features a high static pressure rating of 200 psig (13.8 bar). Weatherproof, UL type 4X, enclosure for dust laden, outdoor, or wash-down installation environments. Externally adjustable set point, integral mounting flange and a removable electrical terminal block for quick and easy installation

Service: Compatible gases and liquids.
Wetted Materials: Connection: Brass; Diaphragm: Fluoroelastomer.
Temperature Limits: 30 to 140°F (-1 to 60°C).
Pressure Limits: Maximum static pressure: 200 psig (13.8 bar); maximum differential pressure: 1.25 x model’s highest set point.
Enclosure Rating: Weatherproof UL type 4X (IP65).
Repeatability: ±2% of full range.
Switch Type: SPDT snap switch.
Electrical Rating: 5 A @ 125/250 VAC, 5 A res. @ 30 VDC.
Electrical Connection: Removable terminal block.
Conduit Connection: 0.871" diameter hole for 1/2" conduit fitting.
Process Connection: 1/4" NPT female.
Mounting Orientation: Ports on horizontal plane, ±10°.
Set Point Adjustment: External screw.
Housing Materials: Body: Aluminum; Housing: Polycarbonate; Cover: 300 SS.
Vibration and Shock: Set point repeats after 2.5 Gs, 5 to 500 Hz. Set point repeats after a 15 Gs, 10 millisecond duration.
Altitude Limit: 6560 ft (2000 m).
Humidity Limit: 80% (non-condensing).
Pollution Degree: 2.
Environment: Intended for indoor and outdoor use.
Weight: 1 lb 3 oz (0.54 kg).
Agency Approvals: CE, cULus.